0 items Tech Support

PCVS-1 - Potter PIV & Butterfly Valve Supervisory Switch

PCVS-1 - Potter PIV & Butterfly Valve Supervisory Switch
Manufacturer:  Potter  SKU:  PCVS-1
Rating: [0]   Write a Review | Read Reviews
In Stock
Usually leaves our warehouse the same business day.
Price:  $62.95

Image Viewer  Show Picture 1
stuff

The Model PCVS is a weather proof and tamper resistant switch for monitoring the open position of fi re sprinkler control valves of the post indicator, butterfl y and other types. Depending on the model, one or two SPDT (Form C) contacts are provided which will operate when the valve position is altered from an open state. The unit mounts in a 1/2" NPT tapped hole in the post indicator or butterfl y valve housing. The device is engaged by the indicating assembly of the post indicator or the operating mechanism of the butterfl y valve, actuating switch(es) when the valve is fully open. The unit should be installed where it is accessible for service. The cover is held in place by two tamper resistant screws that require a special tool to remove. The tool is furnished with each device and should be left with the building owner or responsible party. Replacement or additional cover screws and hex keys are available.

Optional Cover Tamper Switch
A field installable cover tamper switch is available as an option which may be used to indicate removal of the cover.

Testing
The PCVS and its associated protective monitoring system should be tested in accordance with applicable NFPA codes and standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently).

Rating: (0.00)   # of Ratings: 0   

There are no comments for this product.
Dimensions 4.75"L x 2.25"W x 8.2"H (stem extended)
12,1cm L x 5,7cm W x 18,3cm H
Weight 1.35 lb. (0,61 kg.)
Enclosure Cover - Die-Cast
Finish - Red Spatter Enamel
Base - Die Cast Zinc
All parts have corrosion resistant finishes
Cover Tamper Tamper Resistant Screws, Optional cover tamper switch kit available
Mounting 1/2" NPT
Contact Rating PCVS-1: One set of SPDT (Form C)
15 Amps at 125/250VAC
2.5 Amps at 30VDC resistive
Environmental Limitations -40°F to +140°F (-40°C to 60°C)
NEMA 4 and NEMA 6P Enclosure (IP67) when used with appropriate watertight conduit fittings.
Indoor or Outdoor Use (Not for use in hazardous locations. See bulletin no. 5400694 PIVS-U-EX for hazardous locations.)
Accessories

Data Sheet
Downloads: 176
Size: 477 KB



Limited Support

In most cases, the installation or expansion of a commercial fire alarm system is determined by code requirements. There is federal, state, and local codes that come into play, specifying who must install fire alarm equipment, what type of equipment must be installed, where and how it must be installed. Failing to comply fully with any of these codes can result in denial of occupancy permits, fines, legal and financial liability.

Sorry we do not offer technical support for these products because of local codes that come into play specifying who must install fire alarm equipment and where and how it must be installed. To read more, visit the National Fire Alarm and Signaling Code website.