SPECIFICATIONS:
Power
- 3V lithium battery (Duracell DL123A, Panasonic CR123A, Sanyo CR123A, Varta CR123A)
- Operating temperature: 40° to 140°F (6° to 60°C)
- Rate-of-rise temperature: 15°F (8°C) increase per minute (NOTE: Rate-of-rise sensor does not operate above 38°C)
- Fixed temperature: 135°F (57°C)
- Maximum spacing: 50 ft x 50 ft UL, 30 ft x 30 ft FM (refer to National Fire Alarm Code Standard NFPA 72 for application requirements)
- Dimensions: 4.4" diameter, 2/2" deep
AGENCY LISTINGS
WIRELESS TRANSMISSION PATH TEST
A good RF transmission path must be established from the proposed mounting location before permanently installing the detector. To determine that there is a good signal reception from the proposed location, perform the test procedure described in the installation instructions procedure.
MOUNTING THE DETECTOR
You can mount the 5809 on a wall or ceiling within the protection area:
- Wall mounting: Mount the detector 4" - 6" from the ceiling
- Ceiling mounting: Mount the detector at least 4" from any wall. Make sure the normal ceiling temperature will not exceed 100°F.
- Refer to NFPA Standard 72 for detector spacing and other requirements. Maximum spacing for UL installations is 50' x 50'
- Avoid mounting the detector near heat generating devices (e.g. ovens, heat vents, furnaces, boilers)
IMPORTANT: Heat detectors should be used for property protection. Reliance should not be placed solely on heat detectors for life safety. When life safety is involved, smoke detectors MUST also be used. Detectors must not be painted.
Testing the detector
The test procedure should be performed to determine a good RF transmission path and again after installation is completed.
CAUTION: The fixed temperature sensor is intended for one-time use. Prolonged heat during testing can damage the unit. If used carefully following the instructions described below, the heat from a portable hair dryer can be used to test the unit. If the round disk on top of the detector detaches, the detector must be replaced.
- Activate the control panel's test mode
- Use either method (a) or (b) or activate the detector:
(a) Press and release the activation button on the PC board assembly OR
(b) Holding a portable hair dryer about 12 to 18 inches away from the detector, turn the dryer on and aim the warm air at the side of the detector.
CAUTION: Aiming the dryer directly at the round disk on the detector can damage the unit to be replaced.
- The system's keypad should beep and the detector's ID should be displayed
- Exit the control's test mode
FCC Notice
FCC ID: CFS 8DL 5809
This device complies with part 15 of FCC rules.
Operation is subject to the following conditions:
(1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. |